Connecting hardware coupling2 | B&S type K |
Leakage distance inch (mm) | 15 1/8 (385) |
Combined mechanical & electrical strength, lb (kN) | 36000(160)/48000 (178) |
Mechanical impact strength, lb x inch (N·m) | 400 (45) |
Residual strength, lb (kN) | 21580(96) |
Low-frequency dry flashover, kV2 | 80 |
Low-frequency wet flashover, kV2 | 50 |
Critical impulse flashover, positive, kV2 | 125 |
Critical impulse flashover, negative, kV2 | 130 |
R.I.V. test voltage, rms to ground, kV 2 Maximum RIV at 1000 kHz, μV | 10/50 |